3-Phase kW to Amps Calculator & Cable Sizer

Calculate electric motor full load current (FLC), recommended starter types, breaker ratings, and copper or aluminum cable cross-sections in sq mm.

Motor Current & Cable Selection Tool
Electrical Sizing Output
Full Load Current (FLC)
0.00 A
Recommended Cable Size
-
Motor Rating (kW / HP)
-
Component Recommended Specification Standard Engineering Basis
Starter Recommendation - Based on starting inrush limit (DOL vs Star-Delta)
Recommended MCB/MPCB Rating - 1.5x Full Load Current (Motor-Duty Type D curve)
Advertisement
Google AdSense In-Article Unit

The Engineering Math Behind Motor Sizing

Correctly sizing conductors for three-phase AC induction motors is essential to avoid thermal insulation degradation, excessive voltage drops across long runs, and catastrophic motor burnouts.

Three-Phase Motor Current Formula

FLC (Amps) = (Power in kW × 1000) / [√3 × Voltage (V) × Power Factor × Efficiency]
For 415V 3-Phase: Amps ≈ kW × 1.8 (Quick Estimation Rule of Thumb)

Copper vs. Aluminium Conductor Selection

While copper offers superior electrical conductivity and mechanical flexibility, aluminium is substantially more economical for high-current industrial feeder runs (above 16 sq mm).

Motor Rating (kW) FLC (Amps @ 415V) Copper Cable (Armoured) Aluminium Cable (Armoured)
3.7 kW (5 HP) ~7.2 A 1.5 sq mm 2.5 sq mm
7.5 kW (10 HP) ~14.5 A 2.5 sq mm 4.0 sq mm
15 kW (20 HP) ~28 A 6.0 sq mm 10 sq mm
30 kW (40 HP) ~55 A 16 sq mm 25 sq mm
45 kW (60 HP) ~82 A 25 sq mm 35 sq mm

Frequently Asked Questions (FAQ)

Under standard Indian electricity regulations and IS 1255, the steady-state voltage drop from the main distribution board (MDB) to motor terminals should not exceed 3% for lighting and 5% for industrial motive power circuits.
Yes, using a Single-Phase to Three-Phase Variable Frequency Drive (VFD). A VFD takes 230V single-phase input, rectifies it to DC, and inverts it into 3-phase PWM output at full speed and torque control.